TM 10-8145-222-23
MAINTAINER MAINTENANCE
RECEIVER PRESSURE SOLENOID VALVE
REPAIR, REPLACE
INITIAL SETUP:
Tools and Special Tools
References
TM 10-8415-222-10
Refrigeration Equipment
Tool Kit (supplement) (WP 0096, Table 2, Item 7)
Service Refrigeration Ordnance
TM 10-8145-222-23P
Equipment Condition
Personnel Required
Refrigeration unit shut down (TM 10-8415-222-10)
Utilities Equipment Repairer
REPAIR
WARNING
Compressor lubricating oil is caustic and can cause severe injury to skin and eyes.
Wear gloves and protective face shield whenever contact with compressor lubricating
oil is possible. If contact with eyes is made, flush eyes and seek immediate medical
attention. If contact with skin is made, wash affected area of skin with soap and
water.
NOTE
Repair of the receiver pressure solenoid valve is limited to replacement of the
solenoid coil. Perform the following steps to replace the solenoid coil.
WARNING
Falling from the roof of the MTRCS can cause serious personal injury or death. Keep
three points of contact on the MTRCS at all times.
3. Remove top-middle panel (WP 0013, Remove).
4. Tag and disconnect electrical connector (Figure 1, Item 1) from receiver pressure solenoid coil (Figure 1,
Item 2).
0064-1