TM 10-8145-222-23
0064
REPLACE CONTINUED
WARNING
Many of the chemicals used while soldering are toxic. Avoid prolonged exposure to
fumes. Wear rubber gloves and eye protection. Failure to wear proper protective
clothing may result in skin irritation and/or serious eye injury. Wash hands with soap
and water after handling solder. If inhaled, move soldier to fresh air and seek medical
attention. If contact with skin or eyes is made, flush with clean water and seek
medical attention. Failure to observe this warning may result in serious injury to
personnel.
CAUTION
Use care when soldering and desoldering components into the system so as not to
overheat the component being soldered, or surrounding components. Wrapping the
component to be soldered in wet rags will act as a heat sink and minimize exposure
to heat.
7. Desolder each end of 1/4-inch receiver pressure solenoid valve (Figure 2, Item 7) from 1/4-inch tube (Figure 2,
Item 5 and Item 6).
8. Remove valve (Figure 2, Item 7).
9. Install replacement receiver pressure solenoid valve (Figure 2, Item 7) and solder in two fittings to secure valve
to 1/4-inch tube (Figure 2, Item 5 and Item 6).
10. Install receiver pressure solenoid valve coil (Figure 2, Item 2) in accordance with this WP.
11. Perform refrigerant leak check (WP 0014, Service).
12. Perform evacuation and dehydration (WP 0014, Service).
13. Charge system with refrigerant (WP 0014, Servicing).
14. Install top-middle panel (WP 0013, Install).
15. Install top-left panel (WP 0013, Install).
WARNING
Falling from the roof of the MTRCS can cause serious personal injury or death. Keep
three points of contact on the MTRCS at all times.
16. Access top of MTRCS using roof access provided; then crawl around refrigeration unit to access run/stop switch
located at right front corner of refrigeration unit through top grill.
18. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
END OF TASK
END OF WORK PACKAGE
0064-5/6 blank