Figure 3. Speed Control Solenoid Removal.
MAINTAINER MAINTENANCE EVAPORATOR BLOWER MOTOR REPLACE

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  399    400    401    402    403  404  405    406    407    408    409  
img
. . .
TM 10-8145-222-23
0042
REPLACE CONTINUED
8. Operate MTRCS to verify proper operation (TM 10-8415-222-10, Operating Procedures).
9. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
Remove Speed Solenoid Bracket
1. Remove muffler (WP 0039, Remove).
2. Remove speed solenoid per this WP.
3. Remove two bolts (Figure 3, Item 10) and lock washers (Figure 3, Item 11) securing aft side of solenoid mount
bracket (Figure 3, Item 9) to engine (Figure 3, Item 8).
4. Remove one bolt (Figure 3, Item 10), and lock washer (Figure 3, Item 11), spacer (Figure 3, Item 13), lock
washer (Figure 3, Item 14), and nut (Figure 3, Item 15) securing forward side of solenoid mount bracket
(Figure 3, Item 9) to engine (Figure 3, Item 8).
5. Remove solenoid mount bracket (Figure 3, Item 9).
6. Install solenoid mount bracket (Figure 3, Item 9) and secure forward side to engine (Figure 3, Item 8) using one
bolt (Figure 3, Item 10), and lock washer (Figure 3, Item 11), spacer (Figure 3, Item 13), lock washer (Figure 3,
Item 14), and nut (Figure 3, Item 15).
7. Secure aft side of solenoid mount bracket (Figure 3, Item 9) to engine (Figure 3, Item 8) using two bolts
(Figure 3, Item 10) and lock washers (Figure 3, Item 11).
8. Install speed solenoid per this WP.
9. Install muffler (WP 0039, Install).
END OF TASK
TEST
1. Reconnect battery (WP 0053).
WARNING
Approved hearing protection must be worn when operating the MTRCS diesel
engine. Failure to observe this precaution may result in severe and permanent
hearing loss.
2. Start refrigeration unit using diesel engine mode (TM 10-8415-222-10, Operating Procedures). The diesel
engine should operate in low speed and transition to high speed.
3. Shut down refrigeration unit (TM 10-8415-222-10, Operating Procedures).
4. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
END OF TASK
END OF WORK PACKAGE
0042-4