Figure 2. Condenser to Receiver 3/8-Inch Check Valve
8. Carefully align piping (Figure 3, Item 2) with 1/4-inch check valve

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  643    644    645    646    647  648  649    650    651    652    653  
img
. . . . .
TM 10-8145-222-23
0067
REPLACE CONTINUED
Figure 2. Condenser to Receiver 3/8-Inch Check Valve Replacement.
Hot Gas Line to Receiver 1/4-Inch Check Valve
WARNING
Compressor lubricating oil is caustic and can cause severe injury to skin and eyes.
Wear gloves and protective face shield whenever contact with compressor lubricating
oil is possible. If contact with eyes is made, flush eyes and seek immediate medical
attention. If contact with skin is made, wash affected area of skin with soap and
water.
1. Recover refrigerant (WP 0014, Service).
2. Disconnect battery (WP 0053, Disconnect).
3. Remove front panel assembly to gain access to receiver (WP 0013, Remove).
4. Remove left-side panel (WP 0013, Remove).
CAUTION
Use care when removing the tubing away from the check valve. The tubing can be
easily bent or kinked if care is not exercised.
5. Loosen flare nut (Figure 3, Item 1) and remove piping (Figure 3, Item 2) away from 1/4-inch check valve
(Figure 3, Item 3).
6. Loosen and remove 1/4-inch check valve (Figure 3, Item 3) from receiver.
7. Install new 1/4-inch check valve (Figure 3, Item 3) onto receiver and tighten.
0067-5