Evaporator Heater Relay Replace
Panel Assembly Replace (Overload Protector (OL) and Motor Contactor (MC))

TECHNICAL MANUAL FOR MULTI-TEMPERATURE REFRIGERATED CONTAINER SYSTEM
Page Navigation
  787    788    789    790    791  792  793    794    795    796    797  
img
. .
TM 10-8145-222-23
0079
REPAIR CONTINUED
6. Reconnect battery negative (-) terminal (WP 0053, Connect).
7. Operate unit in accordance with normal operating procedures to verify proper operation after replacement of
time delay (TM 10-8415-222-10, Operating Procedures).
8. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
Flashing Relay and Electric Motor Relay Replace
1. Locate flashing relay (FLR) (Figure 7, Item 1), electric motor relay 1EMR (Figure 7, Item 2), and 2EMR
(Figure 7, Item 3) on the back panel.
2. Tag and remove 6 wires (Figure 7, Item 4) on the relay.
3. Remove two screws (Figure 7, Item 5), washers (Figure 7, Item 6) and FLR (Figure 7, Item 1), 1EMR (Figure 7,
Item 2), or 2EMR (Figure 7, Item 3) relay.
Figure 7. FLR, 1EMR and 2EMR Relays.
0079-12