TM 10-8145-222-23
0041
REPLACE CONTINUED
Install Run Solenoid
WARNING
RTV may cause eye and skin irritation. Over frequent or extended periods of use,
RTV may cause irritation to the respiratory system. Wear eye protection and gloves
when using RTV.
1. Apply thin bead of RTV to both sides of new solenoid gasket (Figure 4, Item 9).
2. Install new run solenoid (Figure 4, Item 8) and new gasket (Figure 4, Item 9) to engine housing and secure
using two hex screws (Figure 4, Item 6) and new lock washers (Figure 4, Item 7).
3. Torque hex screws (Figure 4, Item 6) to 7 foot-pounds (WP 0091).
4. Connect run solenoid electrical connector (Figure 4, Item 4) to engine harness (Figure 4, Item 5) as tagged.
5. Reconnect air inlet hose (Figure 4, Item 2) to engine air inlet and secure using clamp (Figure 4, Item 1).
6. Tighten clamp (Figure 4, Item 1).
7. Install top-right panel (WP 0013, Install).
8. Place emergency stop switch (Figure 1, Item 2) in PULL TO START position.
WARNING
Falling from the top of the MTRCS can result in serious injury or death to personnel.
Whenever performing maintenance on top of the MTRCS, always maintain three
points of contact to aid in stability. Never attempt to walk backwards while on top of
the container.
9. Climb off MTRCS using roof access provided.
10. Install right-side panel (WP 0013, Install).
11. Install front panel assembly (WP 0013, Install).
12. Place POWER ON/DOWN switch (Figure 1, Item 2) on control panel to ON position.
13. Start refrigeration unit and allow unit to run for five minutes to verify proper operation (TM 10-8415-222-10,
Operating Procedures).
14. Place MTRCS back into desired mode of operation (TM 10-8415-222-10, Operating Procedures).
0041-4