TM 10-8145-222-23
MAINTAINER MAINTENANCE
STANDBY MOTOR
(MTRCS02 ONLY)
REPLACE
INITIAL SETUP:
Tools and Special Tools
References
TM 10-8415-222-10
Service Refrigeration Ordnance
Materials/Parts
TM 10-8145-222-23P
Lock Washer (12mm ID) (WP 0111, Item 6)
Equipment Condition
Lock Nut (WP 0111, Item 15)
Machine Key (WP 0111, Item 14)
External electrical power disconnected (TM 10-8415-
222-10)
Personnel Required
Utilities Equipment Repairer (2)
REPLACE
Remove
1. Remove four screws (Figure 1, Item 1) and washers (Figure 1, Item 2) securing standby motor electrical wiring
cover (Figure 1, Item 3) to standby motor (Figure 1, Item 4).
2. Remove cover (Figure 1, Item 3) from standby motor (Figure 1, Item 4).
3. Tag and disconnect electrical wiring (Figure 1, Item 5) from standby motor (Figure 1, Item 4). Remove nut
(Figure 1, Item 10), strain relief (Figure 1, Item 11), and wires from motor. Install nut on strain relief for later use.
4. Remove top-middle panel (WP 0013, Remove).
0077-1